Abstract—A new converter transformer and an inductive
filtering
method are presented to solve the existing
problems of
the traditional converter transformer and the
passive filtering
method of the high-voltage direct current
(HVDC) system. It
adopts the ampere-turn balance of the
transformer as the filtering
mechanism. A tap at the linking point of the
prolonged winding
and the common winding of the secondary
windings is connected
with the LC resonance circuit. It can realize the goal
that once the
harmonic current flows into the prolonged
winding, the common
winding will induct the opposite harmonic
current to balance it by
the zero impedance design of the common
winding and the proper
configuration of LC parameters,
so there will be no inductive
harmonic current in the primary winding.
Moreover, the reactive
power that the converter needs can be partly
compensated in the
secondary winding. Simulation results have
verified the correctness
of the theoretical analysis. The new converter
transformer
can greatly reduce the harmonic content in the
primary winding,
loss, and noise generated by harmonics in the
transformer, and
the difficulty of the transformer’s insulation
design.
Index Terms—Filtering mechanism, harmonic, high-voltage
direct current (HVDC), inductive filtering,
new converter
transformer.
I. INTRODUCTION
THE high-voltage direct
current (HVDC) transmission
system
has been widely used in remote and large power
transmission,
submarine cable transmission, and domain electric
network
interconnection [1]–[3]. HVDC transmission
system
is always made up of a rectifier station, a dc line, and
an
inverter station. During the commutating process, a large
number
of harmonics will be generated by the nonlinear load.
Therefore,
it is necessary to carry out harmonic suppression.
The
traditional HVDC ac passive power filters (PPF) are always
placed
at the converter transformer’s primary side (grid side),
and
the transformer will be adversely affected by harmonics,
which
causes a series of problems, such as additional harmonic
loss,
heat, vibration, and noise [1], [4]–[7]. In addition, in order
to
avoid series/parallel resonance between parallel PPF and
(b) Voltage phasor diagram.
system
impedance, the traditional PPF cannot reach its tuned
point,
which greatly affects the filtering effect [8]–[10]. The active
power
filter (APF) has better filtering effect than the passive
power
filter (PPF), but APF needs a complex regulation and
control
system, especially a large power harmonic-generating
source,
which is inapplicable in current HVDC transmission’s
ac
system [11]–[13]. A patent named coupling-compensation
and
harmonic-shielding converter transformer, that is, the new
converter
transformer, proposes an ideal solution to harmonic
suppression.
II.
PROBLEMS
OF TRADITIONAL CONVERTER TRANSFORMER’S
WIRING MODE AND AC FILTERING SCHEME
As
Fig. 1 shows, the traditional converter transformer and ac
passive
filtering method are commonly used in 12-pulse HVDC
system.
It is clear that the transformer adopts wye/wye/delta
wiring,
and ac filters are placed at the transformer’s primary
side.
Although this kind of converter transformer and passive
filters
are widely applied in HVDC systems, these structures and
designs
still have some disadvantages.
1)
In HVDC transmission systems, the converter is the
main
harmonic-generating source. A three-phase bridge
converter
usually generates characteristic
harmonic
currents at the ac side because of
the
turning of the thyristors [14]. The noncharacteristic
harmonic
currents can also be generated due to some
factors,
such as various unbalances in ac voltages, system
impedance,
and transformer parameters [15]. All the
harmonic
currents will flow in the primary and secondary
windings
of the traditional converter transformer, which
increases
the transformer’s additional heat, vibration, and
NEW
CONVERTER TRANSFORMER AND A CORRESPONDING INDUCTIVE FILTERING METHOD 1427
Fig. 2. New
converter transformer and corresponding inductive filtering
system. (a)
Wiring mode. (b) Voltage phasor diagram. (c) Arrangement of
filters.
noise.
As a result, it increases the added loss, the difficulty
of
insulating design, the capacity of the transformer, and
the
margin of the design capability, which increases the
cost
of the traditional converter transformer.
2)
In the ac system of HVDC, traditional passive filtering
is
the main method of harmonic suppression. However, it
still
has several disadvantages. The most serious one is
that
the series/parallel resonance may occur between the
system
impedance and the passive power filters. This series/
parallel
resonance will result in the amplification of
harmonic
current and harmonic voltage, and it may damage
the
passive power filters and neighboring power equipment
[16],
[17]. To avoid the resonance of the passive
power
filters, the tuned frequency of passive power filters
is
designed slightly away from the dominant harmonic frequency.
However,
it will degrade the performance of the
passive
power filter, and the filtering effect of the traditional
passive
filter cannot be optimal.
III.
TECHNICAL
CHARACTERISTICS OF NEW CONVERTER
TRANSFORMER
AND CORRESPONDING
INDUCTIVE FILTERING METHOD
Fig.
2 shows the new converter transformer and the corresponding
inductive
filtering system, in which, (a) shows the
wiring
mode of the transformer, and its secondary winding
adopts
prolonged-delta wiring. To facilitate our discussion,
the
winding of , , is called
prolonged
winding, and the winding of , , ,
, ,
is called common winding. (b) shows
the
transformer’s voltage phasor diagram, which is used to
discuss
the phase-shifting of the new transformer. (c) shows
the
arrangement of the inductive filters. As can be seen from
(c),
a tap at the linking point of each single-phase prolonged
winding
and common winding is connected with double-tuned
(DT)
filters. The inductive filtering method will be discussed
later
on in this paper.
A. Phase-Shifting Principle
In
order to satisfy the demand of 12-pulse HVDC, the converter
transformer
has to supply 12-phase commutating line
voltage.
The secondary winding of the traditional transformer
adopts
wye/delta wiring, and the phase angle difference between
the
wye winding’s line-voltage and the delta winding’s
line-voltage
has to be 30 , which is shown in Fig. 1(b). As for
the
new converter transformer, according to Fig. 2(b), we can
set
the phase angle difference between the line-voltage
and
the to , and set the phase angle difference
between
the line-voltage and the to . In
this
way, the phase angle difference between the line-voltage
and
the is 30 . So we can deduce that the
phase-shifting
angle should be 15 . Set that the
voltage
value of the primary winding of the new converter
transformer
is , the voltage value of the secondary prolonged
winding
is , and the voltage value of the secondary common
winding
is ; then, according to Fig. 2(b) and sine rule, the
following
can be obtained:
(1)
According
to the above equation, the turn-ratio can be obtained
as
follows:
(2)
in
which , , respectively, represent the turn-ratio of the secondary
prolonged
winding and the common winding to primary
winding.
, , and are the turn number of the primary
winding,
the secondary common winding, and the prolonged
winding,
respectively.
In
the actual HVDC systems, the new converter transformer
can
adopt the single-phase three-winding method. As long as the
relation
of the turn-ratio satisfies (2), the new converter transformer
can
supply 12-phase commutating line voltage and satisfy
the commutating
demand of the 12-pulse converter.
B. Self-Coupling Action
The
secondary prolonged winding and the common winding
of
the new converter transformer adopt self-coupling connection,
which
is similar to the series winding and the common
winding
of autotransformer [17], [18]. According to Fig. 2(c),
set
that the output line-voltage is , the voltage of the common
winding
is and the voltage of the prolonged winding is ;
then,
the following voltage phasor diagram in Fig. 3 can be
obtained.
According
to cosine rule, the output line-voltage can be expressed
as
follows:
(3)
Fig. 3.
Voltage phasor diagram for secondary winding’s analysis.
Fig. 4. New
converter transformer’s single-phase harmonic model.
Then,
the voltage of the secondary prolonged winding is deduced
as
follows:
(4)
The
secondary prolonged and common winding of the new
converter
transformer is electromagnetic coupling, which is
similar
to the series andcommonwinding of the autotransformer.
When
the prolonged winding and the common winding maintain
magnetic
force balance, we can obtain the following relation:
(5)
in
which and are the root-mean-square (RMS) current
of
the secondary prolonged winding and the common winding,
respectively.
Fig.
2(c) shows that the current of the secondary prolonged
winding
is equal to the output current , and its electromagnetic
capacity
can be expressed as follows:
(6)
Meanwhile,
the output capacity can be expressed as follows:
(7)
Then,
the ratio coefficient can be obtained as follows, which
is
used to analyze the material utilizing ratio of the transformer:
(8)
Assuming
that the output line-voltage value of the new
converter
transformer is 110 kV, and voltage value of the secondary
common
winding is 35 kV, then, according to (4)–(8), we
can
obtain the ratio coefficient , which indicates
that
new converter transformer is material saving.
C. Inductive Filtering Mechanism
Fig.
4 shows the single-phase model of the new converter
transformer,
which is used to analyze the inductive filtering
mechanism.
In this figure, indicates the harmonic current
source,
which is also the harmonic current of the secondary
Fig. 5.
Single-phase model of the new converter transformer. (a) Winding arrangement.
(b)
Equivalent circuit.
prolonged
winding. and indicate the harmonic current
of
the primary winding and the secondary common winding, respectively.
Because
of the harmonic current of the secondary
prolonged
winding, the primary winding and the secondary
common
winding will induce harmonic current and to
balance
. According to magnetic force balance, the following
results:
(9)
in
which , , and are the turn number of the primary
winding,
the secondary prolonged winding, and the common
winding,
respectively.
If
the harmonic ampere-turns of the secondary prolonged
winding
and those of the common winding can keep balance,
then
, that is, there will be no induction harmonic
current
in the primary winding. That is to say, the harmonic
currents
only flow in the secondary winding of the new transformer.
To
realize the inductive filtering method, it not only
needs
the full tuning design of the tapping filter, but also needs
the
zero inductance design of the secondary common winding
of
the new converter transformer, which will be analyzed in
the
following equivalent circuit of the single-phase transformer
shown
in Fig. 5.
Fig.
5(a) shows the winding arrangement of the single-phase
model
of the new converter transformer. According to short-circuit
test,
we can measure the short-circuit impedance , ,
and
. Then, the equivalent impedance shown in Fig. 6(b) can
be
expressed as follows:
(10)
By
regulating the winding arrangement shown in Fig. 5(a),
it
can realize the goal that the impedance of the secondary
common
winding is approximately equal to 0 (the resistance
can
be ignored for high-capacity converter transformers). In
Fig.
5(b), the solid arrow and the virtual arrow, respectively, indicate
basic
frequency current and harmonic frequency current.
Under
the specific harmonic frequency of the harmonic current
that
needs suppressing, both of the double-tuned filter and the
harmonic
impedance of the secondary common winding are
approximately
0, so the harmonic current mainly flows into
the
branch of the secondary common winding, and there is
approximately
no harmonic current in the primary winding.
In
addition, under the fundamental frequency, the impedance
of
the filter is capacitive, thus providing reactive power
compensation.
LUO et al.: NEW CONVERTER TRANSFORMER AND A
CORRESPONDING INDUCTIVE FILTERING METHOD 1429
Fig. 6. New
HVDC transmission analogy system with new converter transformer
in
rectifier station and traditional converter transformer in inverter
station.
Fig. 7.
Phase current fast Fourier transform (FFT) of the secondary terminal of
the
traditional and the new converter transformer. (a) FFT of secondary phase
current I corresponding to Fig. 1. (b) FFT of secondary
phase current I
corresponding
to Fig. 2.
IV.
SYSTEM
SIMULATION STUDY
A. Simulation Model
In
order to prove the correctness of the above analyses, according
to
the new HVDC transmission testing system shown
in
Fig. 6, we have established a system simulation model by
using
MATLAB/SIMULINK. Fig. 6 shows the rectifier station
with
the new converter transformer and in the corresponding inductive
filtering
method and the inverter station with the traditional
converter
transformer and in the passive filtering method.
It
is necessary to clarify that the double-tuned filter (DT5/7)
is
not needed when we consider suppressing fifth and seventh
harmonic
currents in the wiring method of the new converter
transformer
in the rectifier station. Here, due to the high content
of
fifth and seventh harmonics, in order to remove their negative
effect
of fifth and seventh harmonics on the converter transformer,
we
have designed the DT5/7. In Fig. 7, HP2 indicates
the
second-order high-pass filter; Zr and Zi, respectively, indicate
the
system impedance of the rectifier and the inverter side,
and
and , respectively, indicate the inductance of the rectifier
and
the inverter side.
B. Contrast Analysis of Simulation Results
Fig.
7 shows the phase current FFT of the secondary terminal
of
the traditional converter transformer and that of the
Fig. 8.
Phase current FFT of the primary terminal of the traditional and the
new
converter transformer. (a) FFT of primary phase current I corresponding
to Fig. 1.
(b) FFT of primary phase current I
corresponding
to Fig. 2.
TABLE I
COMPARISON
OF THE HARMONIC CONTENT OF THE SECONDARY
SIDES
OF
THE NEW
AND THE TRADITIONAL CONVERTER TRANSFORMERS
New
converter transformer. It can be seen that the harmonic content
of
each order of the traditional and the new converter transformers
is
similar, which is determined by the nonlinear load,
that
is, the converter. However, as for the primary phase current
of
the transformer shown in Fig. 8, it can be seen that the primary
phase-current
waveform of the new converter transformer
is
better than that of the traditional one, which is determined
by
the wiring method of the transformer and by the filtering
method.
We can see that adopting the new winding wiring and
the
inductive filtering method can effectively suppress the 5th,
7th,
11th, and 13th harmonic currents that only flow in the secondary
winding
of the new transformer, so the THD shown in
Fig.
8(b) is lower than that in Fig. 8(a). Table I shows the FFT
value
of the exact harmonic contents of Figs. 7 and 8, which further
proves
the correctness of the above analysis.
Fig.
9 shows the phase current FFT at the grid side of the
rectifier
and the inverter station, respectively.We can see that the
waveform
of the phase current in Fig. 9(a) is better than that in
Fig.
9(b), which is caused by the new inductive filtering method.
Considering
the effect of the system impedance, the resonance
point
of the passive filters cannot be reached. So the filtering
effect
is not ideal, as shown in Fig. 9(b). While adopting the
inductive
filtering method, the harmonic currents are confined
by
the coupling-windings of the new converter transformer, so
the
resonance point of the tap filters can be reached. Therefore,
we
can obtain the ideal phase current waveform at the grid side
shown
in Fig. 9(a).Acomparison of the exact harmonic contents
is
shown in Table II.
1430
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008
Fig. 9.
Phase current FFT at the grid side of the rectifier station and the inverter
station,
respectively. (a) FFT of phase current I
at
the grid side of the rectifier
station
corresponding to Fig. 6. (b) FFT of phase current I at the grid side of
the
inverter station corresponding to Fig. 6.
TABLE II
COMPARISON
OF THE HARMONIC CONTENT OF THE GRID SIDES
OF
THE RECTIFIER
STATION
AND THE INVERTER STATION
V. CONCLUSION
In
12-pulse HVDC transmission systems, the secondary
windings
of the new converter transformer adopt prolonged
delta
wiring, which brings about good symmetrical characteristics
to
its structure. Each phase short-circuit impedance can be
equal.
It can facilitate the reliable commutation and the sound
operation
of the converter. The equivalent impedance of the
secondary
common winding is approximately 0, which provides
good
conditions for inductive filtering. The resonance point of
the
tap filters of the new transformer can be reached without the
consideration
of the effect of the system impedance. Simulation
results
verify the correctness of our theoretical analysis, and
show
that the filtering effect of the inductive filtering method
is
better than that of the traditional passive filtering method.
Adopting
the new converter transformer and the corresponding
inductive
filtering method can optimize the structure of HVDC
transmission
systems, greatly reducing the negative effect of
harmonic
on the operation of the transformer and improving
the
filtering effect at the ac side of HVDC systems.
No comments:
Post a Comment